Customization: | Available |
---|---|
Task: | Program |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Local I/O | 24 Channels DC24V DI, 16 Channels Relay DO | ||||
Expandable I/O | 7modules | ||||
High-speed counter | Monophase counter: 3 points, 100KHz Biphase counter: 2 points, 100KHz |
||||
Pulse output | N/A | ||||
Pulse catch | 3points | ||||
Interrupt input | 3 points | ||||
Analog potentiometer | 2, value setting range 0~255 | ||||
User program memory capacity |
120K bytes | ||||
Retain area | 6K bytes | ||||
Input data memory | 512 bytes | ||||
Output data memory | 512 bytes | ||||
Mid-variables memory | 8K bytes | ||||
Global memory | 24K bytes | ||||
Password | Yes | ||||
Real-time clock | Built-in | ||||
Timer | No limit (1ms as minimum unit) | ||||
Counter | No limit (Maximum counting range: 16 bit) | ||||
Basic instructions | 283 | ||||
Function blocks | Over 70 | ||||
Operation speed | 0.65μs (Basic instruction) | ||||
Power supply | 220V AC@50Hz | ||||
Allowed range | 187V AC-242V AC@50Hz | ||||
Current consumption (MAX) | 200mA | ||||
Output voltage | 24V DC | ||||
Allowed range | 22.8V DC-25.2V DC | ||||
Current output | +24VDC (To expansion bus) | 320mA | |||
+24V DC (To the outside) | 400mA | ||||
+5V DC (To expansion bus) | 1300mA | ||||
Short circuit protection | 900mA, 24VDC output | ||||
Input type | Sink/Source | ||||
Input voltage rated value | 24V DC | ||||
Allowed range | 0V DC-30V DC | ||||
Logic 1 signal | 15-30V DC, allowed minimum current 3mA | ||||
Logic 0 signal | 0-5V DC, allowed maximum current 1mA | ||||
Input delay time | <0.6ms (Rated input voltage) | ||||
Isolation mode | Photocoupler isolation | ||||
Isolation group | 3 groups | ||||
Maximum Isolation Voltage | 1500VAC | ||||
Output type | Relay | ||||
Output voltage | 24V DC or 24 V AC -230V AC | ||||
Allowed range | 5V DC-30V DC or 5V AC-250V AC | ||||
Common end output current total | <10A | ||||
Output switch capacity | 2A, resistance load | ||||
Minimum load | 10mA (contact voltage 5VAC or 5VDC) | ||||
Over current protection | N/A | ||||
Contact impedance | <0.2Ω | ||||
Isolation group | 4 groups | ||||
Isolation voltage between coil and contact |
3000VAC, 1 minute, leakage current 1mA | ||||
Isolation voltage between contacts | 750VAC, 1 minute, leakage current 1mA | ||||
Isolation resistance (minimum) | 100MΩ between contacts or between coil and contact under 500VDC |
||||
Contact switch delay time | <10ms | ||||
Contact switch frequency (maximum) |
1Hz | ||||
Relay mechanical life | No load: over 10,000,000 times; Rated Resistive load 2A: over 100,000 times |